TN160038 VN19 was born EB due to F9645 was born Logical and change Physical Occupied hold, later TN16 VN19 served Inspection. Train and moving through the normal and F9645 Physical Occupied disappear, time 06: 07. TN01 VN11 was born and EB F9645 Physical Occupied. Hold, appointed IM / AIM, time 06:12. So Siemens / SIG change Card Receiver F9645 result F9645 also show Physical Occupied hold, approve all the trains move through. RM1 - > ATO Mode to normal service, time 08: 17.So the improvement of new voltage F9645 show normal status, check train moving through with ATO Mode normally, time 10: 00. So take off. Card Receiver 1.2 to adjust the voltage from the set 34.2 V. Down on the 17.2 V.So close, the most standard (standard 10-12 V.). Check the train can move through the normally, time 10: 44. So the improvement voltage is under the terms there is Standby until the end of the service. Resume Normal
time 12:15. TN10 VN16 was born EB of unknown causes. The F9645 is Siemens / SIG inform Reset Card neat voltage adjustment in 24.9, V. F9645 show normal status, train moving through the normally
.