1. check the Sensor probes into a series of series Conductivity Controller due to an unusually high measurements, screen reads 3.4 mS/cm. exceeding standards set so check the series probes. It found that when the new series to cable instead of the usual Cabinet is reading, reading approximately. 1.2-1.4 mS/cm. but when the new set of cables to connect them to the original cables are connected at the point of the original temple. Finds the value back up 3.4 mS/cm. similar to the old series probes again, it therefore follows that the cables be connected with problems because of cable, as the cable cord not suitable to continue the probe. Need to change the line per line instead of a new. Find the normal reading. Read on for about 1.4 mS/cm, which is in the normal value of the Condenser water system.