Before the update/revision after the installation of the device channels bring in natural light.Design and improve systems, VRF cooling and Solar Air.Air conditioning systems of office buildings, Corporate Communications Division was originally a large split air conditioning system installed as well as the average performance of 24.76 1.09 kW per ton of cooling, which is higher.The scope of research is defined is not higher than 0.6 kW per ton of cooling, it must continue to improve performance. By design, the Vice President and small office rooms location is South West of the building, it is suitable to install a Solar Air conditioning systems due to placement of condenser in positions that can get sunlight all day to reduce the burden of work of the compressor and other system installed individual VRF. Size: 18.75 tons total refrigeration Condensing Unit has a number of series 3. Each set contains 3 compressor series Working together with the compressor every batch can adjust the level of work in a server control, set ด้ย to conserve energy during the time the liability of bran check variable.After the design improve air conditioning split into the VRF air conditioning system and a Solar Air Conditiong. Energy consumption after update 1.09 from kW per ton cooling only 0.57 kW per ton cooling conform to the scope of the research project must have a value no higher than 0.6 kW per ton of cooling in consideration of air quality criteria and Thermal Comfort inside the building as well.