In the figure COP is, increased after the controller is turned on and system goes to another steady-state without severely. Unstable behavior. Fig. 5 (b) shows the response of cooling capacity in the same experiment with that of Fig. 5 (a). In both. Figures the controlled, parameters do not diverge or behave unstably.The increase of COP can be explained by ratio of the increments of cooling capacity and compressor power consumption. As. Stated the cooling, capacity of the system is maintained at constant value 5 kW but 'specific cooling capacity of refrigerant.' Varies according to change, of pressure temperature and mass flow rate. In the case of Fig. 5 the expansion, valve opening. Changes from 11.6% to some controlled value and finally the opening was reduced to about 10.95% (Fig. 5 (d) and gas-cooler pressure was. Upraised (Fig. 6).
.The COP will increase after the open control system and are fixed. Without a violent behavior, unstable image 5 (b) shows the response capacity in the same cold experiment of the image 5. ) both in numbers,Control parameters are different, or be unstably. The increase of the police can be explained. The proportion of the increase of production and energy use, as described, the refrigeration compressorThe cooling capacity of the system will remain constant. 5 but 'only' cooling capacity of the vapor cleaning the cooler to vary according to the change of pressure. Temperature and mass flow rate in the case of Figure 5.116% to control values, and finally released has dropped to about 10.95% (picture 5 (D) and pressure gas cooler is upraised (Picture 6).
การแปล กรุณารอสักครู่..