In the figure, COP is increased after the controller is turned on and  การแปล - In the figure, COP is increased after the controller is turned on and  อังกฤษ วิธีการพูด

In the figure, COP is increased aft

In the figure, COP is increased after the controller is turned on and system goes to another steady-state without severely unstable behavior. Fig. 5(b) shows the response of cooling capacity in the same experiment with that of Fig. 5(a). In both figures, the controlled parameters do not diverge or behave unstably. The increase of COP can be explained by ratio of the increments of cooling capacity and compressor power consumption. As stated, the cooling capacity of the system is maintained at constant value 5 kW but ‘specific’ cooling capacity of refrigerant varies according to change of pressure, temperature and mass flow rate. In the case of Fig. 5, the expansion valve opening changes from 11.6% to some controlled value and finally the opening was reduced to about 10.95% (Fig. 5(d)) and gas-cooler pressure was upraised (Fig. 6).
นรูป COP จะเพิ่มขึ้นหลังจากควบคุมเปิดและระบบจะคงที่อื่น โดยไม่มีพฤติกรรมรุนแรงที่ไม่เสถียร ภาพที่ 5 ( b ) แสดงให้เห็นการตอบสนองความเย็นความจุในการทดลองเดียวกันกับที่ของภาพที่ 5 ( ) ทั้งในตัวเลข , ควบคุมพารามิเตอร์ไม่แตกต่าง หรือทำตัว unstably .การเพิ่มขึ้นของตำรวจ สามารถอธิบายได้ โดยสัดส่วนของการเพิ่มขึ้นของการผลิตและการใช้พลังงานคอมเพรสเซอร์ทำความเย็น ตามที่ระบุไว้ , ความเย็นความจุของระบบจะยังคงที่กิโลวัตต์มีค่าคงที่ 5 แต่ ' เฉพาะ ' เย็นความจุของสารทําความเย็นที่แตกต่างกันไปตามการเปลี่ยนแปลงของความดัน อุณหภูมิและอัตราการไหลของมวล ในกรณีของรูปที่ 5 การขยายตัววาล์วเปิดการเปลี่ยนแปลงจาก 116 % เพื่อควบคุมค่าและในที่สุดก็เปิดตัวได้ลดลงไปประมาณ 10.95 % ( ภาพที่ 5 ( D ) และความดันแก๊สเย็นเป็น upraised ( ภาพที่ 6 )
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (อังกฤษ) 1: [สำเนา]
คัดลอก!
In the figure, COP is increased after the controller is turned on and system goes to another steady-state without severely unstable behavior. Fig. 5(b) shows the response of cooling capacity in the same experiment with that of Fig. 5(a). In both figures, the controlled parameters do not diverge or behave unstably. The increase of COP can be explained by ratio of the increments of cooling capacity and compressor power consumption. As stated, the cooling capacity of the system is maintained at constant value 5 kW but 'specific' cooling capacity of refrigerant varies according to change of pressure, temperature and mass flow rate. In the case of Fig. 5, the expansion valve opening changes from 11.6% to some controlled value and finally the opening was reduced to about 10.95% (Fig. 5(d)) and gas-cooler pressure was upraised (Fig. 6).On COP will increase after opening and control system will be fixed. Without radical behaviour, unstable image 5 (b) shows a cool response capacity in the same trial of 5 images (), both in numbers, and control parameters are different, or make a. Unstably. an increase of the police can be explained by the proportion of the increase of the production and use of energy and refrigerating compressor as specified, cooling capacity of the system will remain at a constant value of 5 kW, but only ' cool ' capacity of refrigerating substances that vary according to changes of pressure, temperature and mass flow rate. In the case of Figure 5 expansion valve open to change from 116% to control and eventually launched the reduced to approx. 10.95% (Figure 5 (D) evening and gas pressure is upraised (6 images)
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 2:[สำเนา]
คัดลอก!
In the figure, COP is increased after the controller is turned on and system goes to another steady-state without severely unstable behavior. Fig. 5 (b) shows the response of cooling capacity in the same experiment with that of Fig. 5 (a. ). In both figures, the controlled parameters do not diverge or behave unstably. The increase of COP can be explained by ratio of the increments of cooling capacity and compressor power consumption. As stated, the cooling capacity of the system is maintained at constant value. 5 kW but 'specific' cooling capacity of refrigerant varies according to change of pressure, temperature and mass flow rate. In the case of Fig. 5, the expansion valve opening changes from 11.6% to some controlled value and finally the opening was reduced to. about 10.95% (Fig. 5 (d)) and gas-cooler pressure was upraised (Fig. 6).
The COP will increase after the launch control system will continue elsewhere. Without violence unstable picture 5 (b) shows the response of cooling capacity in the same experiment as that of Figure 5 (a) the number, the control parameter is different or behave unstably. Adding. the police Can be explained The proportion of the increase in the production and consumption of refrigeration compressors. As stated, the cooling capacity of the system is maintained at a constant 5 kW, but 'only' cooling capacity of the cooling that varies according to the change of pressure. Temperature and mass flow rate. In the case of Figure 5, the expansion valve change from 116% to control and eventually launch has been reduced by about 10.95% (Figure 5 (D), and the gas cooler is upraised (Figure 6. )
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 3:[สำเนา]
คัดลอก!
In the figure COP is, increased after the controller is turned on and system goes to another steady-state without severely. Unstable behavior. Fig. 5 (b) shows the response of cooling capacity in the same experiment with that of Fig. 5 (a). In both. Figures the controlled, parameters do not diverge or behave unstably.The increase of COP can be explained by ratio of the increments of cooling capacity and compressor power consumption. As. Stated the cooling, capacity of the system is maintained at constant value 5 kW but 'specific cooling capacity of refrigerant.' Varies according to change, of pressure temperature and mass flow rate. In the case of Fig. 5 the expansion, valve opening. Changes from 11.6% to some controlled value and finally the opening was reduced to about 10.95% (Fig. 5 (d) and gas-cooler pressure was. Upraised (Fig. 6).
.The COP will increase after the open control system and are fixed. Without a violent behavior, unstable image 5 (b) shows the response capacity in the same cold experiment of the image 5. ) both in numbers,Control parameters are different, or be unstably. The increase of the police can be explained. The proportion of the increase of production and energy use, as described, the refrigeration compressorThe cooling capacity of the system will remain constant. 5 but 'only' cooling capacity of the vapor cleaning the cooler to vary according to the change of pressure. Temperature and mass flow rate in the case of Figure 5.116% to control values, and finally released has dropped to about 10.95% (picture 5 (D) and pressure gas cooler is upraised (Picture 6).
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: