1ELECTRIC MOTOR CONTROLSOnce the proper motor is selected, understandi การแปล - 1ELECTRIC MOTOR CONTROLSOnce the proper motor is selected, understandi อังกฤษ วิธีการพูด

1ELECTRIC MOTOR CONTROLSOnce the pr

1
ELECTRIC MOTOR CONTROLS
Once the proper motor is selected, understanding the many various control devices available and
their uses and limitations becomes an important part related to reliable operation and protection of
the motor and the personnel using the motor.
Motor Control Topics
There are four major motor control topics or categories to consider. Each of these has several
subcategories and sometimes the subcategories overlap to some extent. Certain pieces of motor
control equipment can accomplish multiple functions from each of the topics or categories.
C The four categories include:
1) Starting the Motor
Disconnecting Means
Across the Line Starting
Reduced Voltage Starting
2) Motor Protection
Overcurrent Protection
Overload Protection
Other Protection (voltage, phase, etc)
Environment
3) Stopping the Motor
Coasting
Electrical Braking
Mechanical Braking
4) Motor Operational Control
Speed Control
Reversing
Jogging
Sequence Control
• An understanding of each of these areas is necessary to effectively apply motor control
principles and equipment to effectively operate and protect a motor.
2
MOTOR STARTING
All motors must have a control device to start and stop the motor called a “motor controller”.
Motor Controller
A motor controller is the actual device that energizes and de-energizes the circuit to the motor so
that it can start and stop.
• Motor controllers may include some or all of the following motor control functions:
S starting, stopping, over-current protection, overload protection, reversing, speed
changing, jogging, plugging, sequence control, and pilot light indication.
S Controllers range from simple to complex and can provide control for one motor,
groups of motors, or auxiliary equipment such as brakes, clutches, solenoids, heaters,
or other signals.
Motor Starter
The starting mechanism that energizes the circuit to an induction motor is called the “starter” and
must supply the motor with sufficient current to provide adequate starting torque under worst case
line voltage and load conditions when the motor is energized.
• There are several different types of equipment suitable for use as “motor starters” but only
two types of starting methods for induction motors:
1. Across the Line Starting
2. Reduced Voltage Starting
Across the Line Starting of Motors
Across the Line starting connects the motor windings/terminals directly to the circuit voltage “across
the line” for a “full voltage start”.
• This is the simplest method of starting a
motor. (And usually the least expensive).
• Motors connected across the line are capable
of drawing full in-rush current and
developing maximum starting torque to
accelerate the load to speed in the shortest
possible time.
• All NEMA induction motors up to 200
horsepower, and many larger ones, can withstand full voltage starts. (The electric
distribution system or processing operation may not though, even if the motor will).
Across the Line Starters
3
Figure 26. Manual Starter
There are two different types of common “across the line” starters including
1. Manual Motor Starters
2. Magnetic Motor Starters
Manual Motor Starters
A manual motor starter is package consisting of a horsepower rated switch with one set of contacts
for each phase and corresponding thermal overload devices to provide motor overload protection.
• The main advantage of a manual motor starter is lower cost than a magnetic motor starter
with equivalent motor protection but less motor control capability.
• Manual motor starters are often used for smaller motors - typically fractional horsepower
motors but the National Electrical Code allows their use up to 10 Horsepower.
• Since the switch contacts remain closed if power is removed from the circuit without
operating the switch, the motor restarts when power is reapplied which can be a safety
concern.
• They do not allow the use of remote control or auxiliary control equipment like a magnetic
starter does.
Magnetic Motor Starters
A magnetic motor starter is a package consisting of a contactor capable of opening and closing a set
4
Figure 27. Magnetic Starter
of contacts that energize and de-energize the circuit to the motor along with additional motor
overload protection equipment.
C Magnetic starters are used with larger motors (required above 10 horsepower) or where
greater motor control is desired.
• The main element of the magnetic motor starter is the contactor, a set of contacts operated by
an electromagnetic coil.
S Energizing the coil causes the contacts (A) to close allowing large currents to be
initiated and interrupted by a smaller voltage control signal.
S The control voltage need not be the same as the motor supply voltage and is often low
voltage allowing start/stop controls to be located remotely from the power circuit.
• Closing the Start button contact energizes the contactor coil. An auxiliary contact on the
contactor is wired to seal in the coil circuit. The contactor de-energizes if the control circuit
is interrupted, the Stop button is operated, or if power is lost.
• The overload contacts are arranged so an overload trip on any phase will cause the contactor
to open and de-energize all phases.
Reduced Voltage Starting of Motors
Reduced Voltage Starting connects the motor windings/terminals at lower than normal line voltage
during the initial starting period to reduce the inrush current when the motor starts.
5
• Reduced voltage starting may be required when:
S The current in-rush form the motor starting adversely affects the voltage drop on the
electrical system.
S needed to reduce the mechanical “starting shock” on drive-lines and equipment when
the motor starts.
• Reducing the voltage reduces the current in-rush to the motor and also reduces the starting
torque available when the motor starts.
• All NEMA induction motors can will accept reduced voltage starting however it may not
provide enough starting torque in some situations to drive certain specific loads.
If the driven load or the power distribution system cannot accept a full voltage start, some type of
reduced voltage or "soft" starting scheme must be used.
• Typical reduced voltage starter types include:
1. Solid State (Electronic) Starters
2. Primary Resistance Starters
3. Autotransformer Starters
4. Part Winding Starters
5. Wye-Delta Starters
Reduced voltage starters can only be used where low starting torque is acceptable or a means exists
to remove the load from the motor or application before it is stopped.
6
MOTOR PROTECTION
Motor protection safeguards the motor, the supply system and personnel from various operating
conditions of the driven load, the supply system or the motor itself.
C Motor protection categories include
S Overcurrent Protection
S Overload Protection
S Other Types of Protection.
• The National Electrical Code requires that
motors and their conductors be protected
from both overcurrent and overload
conditions.
Overcurrent Protection
Overcurrent protection interrupts the electrical circuit to the motor upon excessive current demand
on the supply system from either short circuits or ground faults.
• Overcurrent protection is required to protect personnel, the motor branch circuit conductors,
control equipment, and motor from these high currents.
• Overcurrent protection is usually provided in the form of fuses or circuit breakers. These
devices operate when a short circuit, ground fault or an extremely heavy overload occurs.
S Most overcurrent sources produce extremely large currents very quickly.
7
0
100
200
300
400
500
600
Full Load Amps (%)
0 1 2 3 4 5 6 7 8 9 10 11 12
Time (Minutes)
Motor Heating Curve
Motor Damage
Allowable Operation Area
Amperage
Time
Motor Current Draw
Motor Running Current
Starting In-Rush Current
Overload Protection
Overload protection is installed in the motor circuit and/or motor to protect the motor from damage
from mechanical overload conditions when it is operating/running.
• The effect of an overload is an excessive rise in temperature in the motor windings due to
current higher than full load current.
C Properly sized overload
protection disconnects the
motor from the power supply
when the heat generated in the
motor circuit or windings
approaches a damaging level
for any reason.
S The larger the overload, the
more quickly the temperature
will increase to a point that is
damaging to the insulation and
lubrication of the motor.
C Unlike common instantaneous type fuses and breakers, overload devices are designed to
allow high currents to flow briefly in the motor to allow for:
C Typical motor starting
currents of 6 to 8 times
normal running current
when starting.
C Short duration overloads
such as a slug of product
going through a system.
S If the motor inlets and outlets are
covered by a blanket of lint or if a
bearing should begin to lock,
excessive heating of the motor
windings will “overload” the
motors insulation which could
damage the motor.
5. The overcurrent device will not react to this low level overload. The motor overload device
prevents this type of problem from severely damaging the motor and also provide protection
for the circuit conductors since it is rated for the same or less current as the conductors.
• Overload protection trips when an overload exists for more than a short time. The time it
takes for an overload to trip depends on the type of overload device, length of time the
overload exists, and the ambient temperature in which the overloads are located.
8
Other Motor Protection Devices
Low Voltage Protection
Low Voltage Disconnects - Protection device operates to disconnect the motor when the supply
voltage drops below a preset value. The motor must be manually restarted upon resumption of
normal supply voltage.
Low Voltage Release - Protection device interrupts the circuit when the supply voltage drops below
a preset value and re-establishes the circuit when the supply voltage returns to normal.
Phase Failure Protection
Interrupts the power in
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (อังกฤษ) 1: [สำเนา]
คัดลอก!
1.ELECTRIC MOTOR CONTROLSOnce the proper motor is selected, understanding the many various control devices available andtheir uses and limitations becomes an important part related to reliable operation and protection ofthe motor and the personnel using the motor.Motor Control TopicsThere are four major motor control topics or categories to consider. Each of these has severalsubcategories and sometimes the subcategories overlap to some extent. Certain pieces of motorcontrol equipment can accomplish multiple functions from each of the topics or categories.C The four categories include:1) Starting the MotorDisconnecting MeansAcross the Line StartingReduced Voltage Starting2) Motor ProtectionOvercurrent ProtectionOverload ProtectionOther Protection (voltage, phase, etc)Environment3) Stopping the MotorCoastingElectrical BrakingMechanical Braking4) Motor Operational ControlSpeed ControlReversingJoggingSequence Control• An understanding of each of these areas is necessary to effectively apply motor controlprinciples and equipment to effectively operate and protect a motor.2.MOTOR STARTINGAll motors must have a control device to start and stop the motor called a "motor controller".Motor ControllerA motor controller is the actual device that energizes and de-energizes the circuit to the motor sothat it can start and stop.• Motor controllers may include some or all of the following motor control functions:S starting, stopping, over-current protection, overload protection, reversing, speedchanging, jogging, plugging, sequence control, and pilot light indication.S Controllers range from simple to complex and can provide control for one motor,groups of motors, or auxiliary equipment such as brakes, clutches, solenoids, heaters,or other signals.Motor StarterThe starting mechanism that energizes the circuit to an induction motor is called the "starter" andmust supply the motor with sufficient current to provide adequate starting torque under worst caseline voltage and load conditions when the motor is energized.• There are several different types of equipment suitable for use as "motor starters" but onlytwo types of starting methods for induction motors:1. Across the Line Starting2. Reduced Voltage StartingAcross the Line Starting of MotorsAcross the Line starting connects the motor windings/terminals directly to the circuit voltage "acrossthe line" for a "full voltage start".• This is the simplest method of starting amotor. (And usually the least expensive).• Motors connected across the line are capableof drawing full in-rush current anddeveloping maximum starting torque toaccelerate the load to speed in the shortestpossible time.• All NEMA induction motors up to 200horsepower, and many larger ones, can withstand full voltage starts. (The electricdistribution system or processing operation may not though, even if the motor will).Across the Line Starters3.Figure 26. Manual StarterThere are two different types of common "across the line" starters including1. Manual Motor Starters2. Magnetic Motor StartersManual Motor StartersA manual motor starter is package consisting of a horsepower rated switch with one set of contactsfor each phase and corresponding thermal overload devices to provide motor overload protection.• The main advantage of a manual motor starter is lower cost than a magnetic motor starterwith equivalent motor protection but less motor control capability.• Manual motor starters are often used for smaller motors - typically fractional horsepowermotors but the National Electrical Code allows their use up to 10 Horsepower.• Since the switch contacts remain closed if power is removed from the circuit withoutoperating the switch, the motor restarts when power is reapplied which can be a safetyconcern.• They do not allow the use of remote control or auxiliary control equipment like a magneticstarter does.Magnetic Motor StartersA magnetic motor starter is a package consisting of a contactor capable of opening and closing a set4.Figure 27. Magnetic Starterof contacts that energize and de-energize the circuit to the motor along with additional motoroverload protection equipment.C Magnetic starters are used with larger motors (required above 10 horsepower) or wheregreater motor control is desired.• The main element of the magnetic motor starter is the contactor, a set of contacts operated byan electromagnetic coil.S Energizing the coil causes the contacts (A) to close allowing large currents to beinitiated and interrupted by a smaller voltage control signal.S The control voltage need not be the same as the motor supply voltage and is often lowvoltage allowing start/stop controls to be located remotely from the power circuit.• Closing the Start button contact energizes the contactor coil. An auxiliary contact on thecontactor is wired to seal in the coil circuit. The contactor de-energizes if the control circuitis interrupted, the Stop button is operated, or if power is lost.• The overload contacts are arranged so an overload trip on any phase will cause the contactorto open and de-energize all phases.Reduced Voltage Starting of MotorsReduced Voltage Starting connects the motor windings/terminals at lower than normal line voltageduring the initial starting period to reduce the inrush current when the motor starts.5.• Reduced voltage starting may be required when:S The current in-rush form the motor starting adversely affects the voltage drop on theelectrical system.S needed to reduce the mechanical "starting shock" on drive-lines and equipment whenthe motor starts.• Reducing the voltage reduces the current in-rush to the motor and also reduces the startingtorque available when the motor starts.• All NEMA induction motors can will accept reduced voltage starting however it may notprovide enough starting torque in some situations to drive certain specific loads.If the driven load or the power distribution system cannot accept a full voltage start, some type ofreduced voltage or "soft" starting scheme must be used.• Typical reduced voltage starter types include:1. Solid State (Electronic) Starters2. Primary Resistance Starters3. Autotransformer Starters4. Part Winding Starters5. Wye-Delta StartersReduced voltage starters can only be used where low starting torque is acceptable or a means existsto remove the load from the motor or application before it is stopped.6.MOTOR PROTECTIONMotor protection safeguards the motor, the supply system and personnel from various operatingconditions of the driven load, the supply system or the motor itself.C Motor protection categories includeS Overcurrent ProtectionS Overload ProtectionS Other Types of Protection.• The National Electrical Code requires thatmotors and their conductors be protectedfrom both overcurrent and overloadconditions.Overcurrent ProtectionOvercurrent protection interrupts the electrical circuit to the motor upon excessive current demandon the supply system from either short circuits or ground faults.• Overcurrent protection is required to protect personnel, the motor branch circuit conductors,control equipment, and motor from these high currents.• Overcurrent protection is usually provided in the form of fuses or circuit breakers. Thesedevices operate when a short circuit, ground fault or an extremely heavy overload occurs.S Most overcurrent sources produce extremely large currents very quickly.7.0.100200300400500600Full Load Amps (%)0 1 2 3 4 5 6 7 8 9 10 11 12.Time (Minutes)Motor Heating CurveMotor DamageAllowable Operation AreaAmperageTimeMotor Current DrawMotor Running CurrentStarting In-Rush CurrentOverload ProtectionOverload protection is installed in the motor circuit and/or motor to protect the motor from damagefrom mechanical overload conditions when it is operating/running.• The effect of an overload is an excessive rise in temperature in the motor windings due tocurrent higher than full load current.C Properly sized overloadprotection disconnects themotor from the power supplywhen the heat generated in themotor circuit or windingsapproaches a damaging levelfor any reason.S The larger the overload, themore quickly the temperaturewill increase to a point that isdamaging to the insulation andlubrication of the motor.C Unlike common instantaneous type fuses and breakers, overload devices are designed toallow high currents to flow briefly in the motor to allow for:C Typical motor startingcurrents of 6 to 8 timesnormal running currentwhen starting.C Short duration overloadssuch as a slug of productgoing through a system.S If the motor inlets and outlets arecovered by a blanket of lint or if abearing should begin to lock,excessive heating of the motorwindings will "overload" themotors insulation which coulddamage the motor.5. The overcurrent device will not react to this low level overload. The motor overload deviceprevents this type of problem from severely damaging the motor and also provide protectionfor the circuit conductors since it is rated for the same or less current as the conductors.• Overload protection trips when an overload exists for more than a short time. The time ittakes for an overload to trip depends on the type of overload device, length of time theoverload exists, and the ambient temperature in which the overloads are located.8.Other Motor Protection DevicesLow Voltage ProtectionLow Voltage Disconnects - Protection device operates to disconnect the motor when the supplyvoltage drops below a preset value. The motor must be manually restarted upon resumption ofnormal supply voltage.Low Voltage Release - Protection device interrupts the circuit when the supply voltage drops belowa preset value and re-establishes the circuit when the supply voltage returns to normal.Phase Failure ProtectionInterrupts the power in
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 2:[สำเนา]
คัดลอก!
1
ELECTRIC MOTOR CONTROLS
Once the proper Motor is Selected, understanding the many Various Control Devices Available and
their uses and limitations Becomes an important Part Related to Reliable Operation and Protection of
the Motor and the Personnel using the Motor.
Motor Control Topics
There are Four Major. motor control topics or categories to consider. Each of these has several
subcategories and sometimes the subcategories Overlap to Some extent. Certain pieces of Motor
Control Equipment Can accomplish multiple functions from each of the Topics or categories.
C The Four categories include:
1) Starting the Motor
Disconnecting Means
Across the Line Starting
Reduced Voltage Starting
2) Motor Protection
overcurrent Protection
Overload Protection
Other Protection (Voltage. , phase, etc)
Environment
3) Stopping the Motor
Coasting
Electrical Braking
Mechanical Braking
4) Motor Operational Control
Speed ​​Control
Reversing
Jogging
Sequence Control
• An understanding of each of these areas is necessary to effectively Apply Motor Control
principles and Equipment to effectively operate and Protect. a Motor.
2
MOTOR Starting
All Motors must have a Control Device to Start and Stop the Motor Called a "Motor Controller".
Motor Controller
A Motor Controller is the Actual Device that energizes and de-energizes the Circuit to the Motor so
that it Can. Start and Stop.
• Motor controllers May include Some or all of the following Motor Control functions:
S Starting, stopping, over-current Protection, overload Protection, reversing, speed
changing, Jogging, plugging, Sequence Control, and Pilot Light indication.
S. Controllers Range from Simple to Complex and Can provide Control for one Motor,
groups of Motors, or Auxiliary Equipment such As brakes, clutches, solenoids, heaters,
or Other Signals.
Motor Starter
The Starting Mechanism that energizes the Circuit to an induction Motor is Called. the "starter" and
must Supply the Motor with sufficient current to provide adequate Starting Torque under worst Case
line Voltage and Load conditions when the Motor is energized.
• There are several different types of Equipment suitable for use As "Motor starters" but only
Two. Starting types of methods for induction Motors:
1. Across the Starting Line
2. Starting Voltage reduced
Across the Starting Line of Motors
Across the Starting Line connects the Motor windings / terminals directly to the Circuit Voltage "Across
the line "for a" full Voltage Start ".
• This is the Simplest method of Starting a
Motor. (And usually the least expensive).
• Motors Connected Across the line are Capable
of Drawing full in-Rush current and
developing maximum Starting Torque to
Accelerate the Load to speed in the Shortest
possible time.
• All NEMA induction Motors up to 200
horsepower,. and many larger ones, can withstand full voltage starts. (The Electric
Distribution System Operation Processing May or not though, even if the Motor Will).
Across the Line Starters
3
Figure 26. Starter Manual
There are Two different types of common "Across the line" starters including
1. Manual Motor Starters
2. Magnetic Motor Starters
Manual Motor Starters
A manual Motor starter is Package consisting of a horsepower rated Switch with one SET of Contacts
for each phase and corresponding Thermal overload Devices to provide Motor overload Protection.
• The main Advantage of a manual Motor starter is Lower cost than. a Magnetic Motor starter
with Equivalent Motor Protection but Less Motor Control capability.
• Manual Motor starters are often used for smaller Motors - typically fractional horsepower
Motors but the National Electrical Code Allows their use up to 10 Horsepower.
• Since the Switch Contacts remain Closed if. Power is removed from the Circuit without
operating the Switch, the Motor Restarts when Power is reapplied which Can be a safety
Concern.
• They do not Allow the use of Remote Control or Auxiliary Control Equipment like a Magnetic
starter does.
Magnetic Motor Starters
A Magnetic. Motor Package consisting of a starter is a contactor Capable of opening and Closing a SET
4
Figure 27. Magnetic Starter
energize and de-energize of Contacts that the Circuit to the Motor Along with Additional Motor
overload Protection Equipment.
C Magnetic starters are used with larger. Motors (required above 10 horsepower) or where
Greater Motor Control is desired.
• The main element of the Magnetic Motor starter is the contactor, a SET of Contacts operated by
an electromagnetic Coil.
S Energizing the Coil causes the Contacts (A) to close. allowing Large Currents to be
initiated and Interrupted by a smaller Voltage Control Signal.
S The Control Voltage Need not be the Same As the Motor Supply Voltage and is often low
Voltage allowing Start / Stop Controls to be located remotely from the Power Circuit.
• Closing. the Start button contact energizes the contactor coil. An Auxiliary Contact on the
contactor is Wired to Seal in the Coil Circuit. The contactor de-energizes if the Control Circuit
is Interrupted, the Stop Button is operated, or if Power is Lost.
• The overload Contacts are arranged so an overload on any phase Trip Will Cause the contactor
to open and de-energize all phases.
Starting Voltage Motors of reduced
Reduced Voltage Starting connects the Motor windings / terminals at Lower than Normal Voltage line
during the initial period to Reduce the inrush current when Starting the Motor starts.
5
• Reduced Voltage Starting May be required when:
The current in-S. Rush form the Motor Starting adversely affects the Voltage Drop on the
Electrical System.
S Needed to Reduce the Mechanical "Starting Shock" on Drive-Lines and Equipment when
the Motor starts.
• Reducing the Voltage reduces the current in-Rush to the Motor and. also reduces the Starting
Torque Available when the Motor starts.
• All NEMA induction Motors Can Will accept reduced Voltage Starting however it May not
provide Enough Starting Torque in Some Situations to Drive certain specific loads.
If the Driven Load or the Power Distribution System Can not accept. a full Voltage Start, Some Type of
reduced Voltage or "Soft" Starting Scheme must be used.
• Typical Voltage reduced starter types include:
1. Solid State (Electronic) Starters
2. Starters primary Resistance
3. Starters autotransformer
4. Part Winding Starters
5. Wye-Delta Starters
Reduced Voltage starters Can only be used where low Starting Torque is Acceptable or a means exists
to Remove the Load from the Motor or Application before it is stopped.
6
MOTOR PROTECTION
Motor Protection safeguards the Motor, the Supply System and Personnel from. Various operating
conditions of the Driven Load, the Supply System or the Motor Itself.
C Motor Protection categories include
S overcurrent Protection
S Overload Protection
S Other Types of Protection.
• The National Electrical Code requires that
Motors and their conductors be Protected
from both overcurrent and. overload
conditions.
overcurrent Protection
overcurrent Protection interrupts the Electrical Circuit to the Motor upon excessive current demand
on the Supply System from either short Circuits or Ground faults.
• overcurrent Protection is required to Protect Personnel, the Motor Branch Circuit conductors,
Control Equipment, and Motor. High Currents from these.
• overcurrent Protection is usually provided in the form of fuses or Circuit Breakers. These
Devices operate when a short Circuit, Ground Fault or an extremely Heavy overload occurs.
S Most overcurrent Sources Produce extremely Large Currents very Quickly.
7
0
100
200
300
400
500
600
Full Load Amps (%)
0 1 2 3 4 5 6 7. 8 9 10 11 12
Time (Minutes)
Motor Heating Curve
Motor Damage
Allowable Operation Area
amperage
Time
Motor Current Draw
Motor Running Current
Starting In-Rush Current
Overload Protection
Overload Protection is installed in the Motor Circuit and / or Motor to Protect the Motor from damage.
from Mechanical overload conditions when it is operating / running.
• The Effect of an overload is an excessive rise in Temperature in the Motor windings Due to
current Higher than full Load current.
C properly sized overload
Protection disconnects the
Motor from the Power Supply
when the. Heat Generated in the
Motor Circuit or windings
approaches a damaging level
for any Reason.
S The larger the overload, the
More Quickly the Temperature
Will increase to a Point that is
damaging to the Insulation and
Lubrication of the Motor.
C Unlike common instantaneous Type fuses. and Breakers, overload Devices are designed to
Allow High Currents to Flow briefly in the Motor to Allow for:
C Typical Motor Starting
Currents of 6 to 8 times
Normal running current
when Starting.
C Short Duration overloads
such As a Slug of product
going Through a. System.
If the S Motor Outlets and inlets are
covered by a Blanket of lint or if a
Bearing should BEGIN to Lock,
excessive Heating of the Motor
windings Will "overload" the
Insulation Motors which could
damage the Motor.
5. The overcurrent device will not react to this low level overload. The Motor overload Device
prevents this Type of Problem from severely damaging the Motor and also provide Protection
for the Circuit conductors since it is rated for the Same or Less current As the conductors.
• Overload Protection trips when an overload exists for More than a short time. . The time it
Takes for an overload to Trip depends on the Type of overload Device, Length of time the
overload exists, and the Ambient Temperature in which the overloads are located.
8
Other Motor Protection Devices
Low Voltage Protection
Low Voltage Disconnects - Protection Device operates. when the disconnect to the Motor Supply
Voltage drops Below a Preset value. The Motor must be manually restarted upon resumption of
Normal Supply Voltage.
Low Voltage Release - Protection Device interrupts the Circuit when the Supply Voltage drops Below
a Preset value and re-establishes the Circuit when the Supply Voltage Returns to Normal.
Phase Failure Protection
Interrupts the. power in
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 3:[สำเนา]
คัดลอก!
1
ELECTRIC MOTOR CONTROLS
Once the proper motor is selected understanding the, many various control devices available and
their. Uses and limitations becomes an important part related to reliable operation and protection of
the motor and the personnel. Using the motor.

Motor Control Topics There are four major motor control topics or categories to consider. Each of these. Has several
.Subcategories and sometimes the subcategories overlap to some extent. Certain pieces of motor
control equipment can accomplish. Multiple functions from each of the topics or categories.
C The four categories include:
1) Starting the Motor
Disconnecting. Means
Across the Line Starting
Reduced Voltage Starting
2) Motor Protection


Overcurrent Protection Overload Protection Other. Protection, (voltagePhase etc)

, Environment 3) Stopping the Motor


Coasting Electrical Braking Mechanical Braking
4) Motor Operational Control
Speed. Control


Reversing Jogging Sequence Control
- An understanding of each of these areas is necessary to effectively apply motor. Control
principles and equipment to effectively operate and protect a motor.

MOTOR 2 STARTING
.All motors must have a control device to start and stop the motor called a "motor controller." Motor Controller

A motor. Controller is the actual device that energizes and de-energizes the circuit to the motor so
that it can start and stop.
* Motor controllers may include some or all of the following motor control functions:
S starting stopping over-current protection,,,, Overload, protectionReversing speed
changing jogging,,,,, plugging sequence control and pilot light indication.
S Controllers range from simple. To complex and can provide control for one motor
groups, of motors or auxiliary, equipment such as brakes clutches solenoids,,,, Heaters
or, other signals.

Motor Starter The starting mechanism that energizes the circuit to an induction motor is called. The "starter." and
.Must supply the motor with sufficient current to provide adequate starting torque under worst case
line voltage and load. Conditions when the motor is energized.
- There are several different types of equipment suitable for use as "motor starters." But only
two types of starting methods for induction motors:
1. Across the Line Starting
2. Reduced Voltage Starting
.Across the Line Starting of Motors
Across the Line starting connects the motor windings / terminals directly to the circuit. Voltage "across
the line." for a "full voltage start".
- This is the simplest method of starting a
motor. (And usually the. Least expensive).
- Motors connected across the line are capable
of drawing full in-rush current and
developing maximum. Starting torque to
.Accelerate the load to speed in the shortest
.
- possible time All NEMA induction motors up to 200
horsepower and many,, Larger ones can withstand, full voltage starts. (The electric
distribution system or processing operation may, not though. Even if the motor will).
Across the Line Starters

Figure 3 26. Manual Starter
There are two different types of common across. " The line. "Starters including
.1. Manual Motor Starters
2. Magnetic Motor Starters
Manual Motor Starters
A manual motor starter is package consisting. Of a horsepower rated switch with one set of contacts
for each phase and corresponding thermal overload devices to provide. Motor overload protection.
- The main advantage of a manual motor starter is lower cost than a magnetic motor starter
.With equivalent motor protection but less motor control capability.
- Manual motor starters are often used for smaller. Motors - typically fractional horsepower
motors but the National Electrical Code allows their use up to 10 Horsepower.
* Since the switch contacts remain closed if power is removed from the circuit without
operating, the switch
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2025 I Love Translation. All reserved.

E-mail: