3. Feeder one of the MDB; MCCB 225 AT / ... AF 120 Sq.mm. line electric circuit supplying power to a group home, SV2, and from dynamometer month in August 2558 were as follows: Phase A = 9.5A Phase B =. 4.9A Phase C = 8.8 a and Distribution Panel within the house SV2 separately as detailed below
- Student Village 2 (Single) 84 rooms equipped with air conditioning, a 1ᶲ, 220V, 12,000 BTU number one machine
- Student Village. 2 (Married) 12 rooms equipped with air conditioning, a 1ᶲ, 220V, 12,000 BTU 2 units
- from air conditioning 1ᶲ, 220 V number 84 + (2 x 12) = 108 machine
from air conditioning Mitsubishi and Trane size. 1ᶲ, 220 V. 12,000 BTU power while running 5.3 a (Max) 108 is air conditioning and electricity 1ᶲ 220 V = 5.3AX 108 = 572.4A the average electricity 3ᶲ = 572.4 3 = 190.8 a / Phase.
- data from the Main Breaker Feeder 1, MCCB 225 aT can also load and power lines buried in size 120 Sq.mm. a metal pipe (228A) can also be used when the air conditioning load size 1ᶲ, 220V.,. 12,000 BTU all behind