2. the overall MDB Cabinet conditions.-Internal and external cabinet conditions found some rust spots, and have an Outgoing Feeder area ever Cabinet fire or Short Circuit inside the Cabinet before. -Cabinet conditions MCCB 1, 6, 7 are also in new condition, MCCB section available 2, 3, 4, 5, there are traces of external conditions ever, Short Circuit or fire inside the Cabinet before.-Cord condition and equipment inside the Cabinet, Outgoing Feeder side conditions found caused a fire or Short Circuit ever inside the Cabinet before.The current conditions. The tape has been used to wrap around the cord to the replacement of the insulation has been damaged.-Cord condition and equipment inside the Cabinet, good condition, the Incoming side still works as usual.-Suggestions -Should be changed to the new cabinet as the Cabinet and internal components. MCCB-2, 3, 4, 5 should be replaced. -The power cable has been damaged, cut out the damaged section and make a plug at the Cable box under the Cabinet.