1. a finding that the heat accumulation area (JOINT) of the BUSDUCT unusually, MAIN circuit BREAKER release of BUSDUCT. check and replace the screw that is TORQUE wrench type point WRENCH set tension at 800 kgf.cm. 2. when found to have accumulated dust or dirt, use a vacuum the dirt away with a clean cloth and check the machine should not be used for cleaning the dust blowing dust will disperse into mist, because embedded in the niches of the Groove/products.3. When you find that the wetlands area HOUSING of BUSDUCT please be careful to remove the liner. Need to unlock a MAIN circuit BREAKER prior to guest's safety work. After the liner is out, check the water drain holes that have dirt clogging or not. Be careful not to chase the MOP water into areas of BUSDUCT because water is a conductor that may cause a short circuit.4. When you find that there is a short circuit of the BUSDUCT or found to have occurred, and the ARC BREAKER circuit breaker. Do not attempt to restore the system in the BREAKER ON it immediately, investigated the MEGA OHM measurement of insulation between PHASE TO PHASE, PHASE BUSDUCT TO GROUND if found defective, immediately notify shelters the BUSDUCT.