- Feedback
- Replace cabinet. And a new cabinet
- MCCB 2, 3, 4, 5 should be replaced
- the cord has been damaged. To cut out the damaged section Cable box and make calls at the cabinet
3. Feeder one of the MDB; MCCB 225 AT / ... AF 120 Sq.mm. wire size range of this power to a group home SV2 from the dynamometer when in August 2558. as follows: Phase a = 9.5A Phase B = 4.9A Phase C = 8.8 a and Distribution Panel within the house SV2 separately as detailed below
- Student Village 2 (Single) 84 rooms equipped with air conditioning, one size. 220V, 12,000 BTU number one machine
- Student Village 2 (Married) 12 rooms equipped with air conditioning, size 1, 220V, 12,000 BTU 2 units
- from air conditioning 1, 220 V number 84 + (2 x 12) =. 108 machines
from Mitsubishi and Trane air conditioning size 1, 220 V. 12,000 BTU power while running 5.3 a (Max) 108 is air conditioning appliances, electric current 1 220 V = 5.3AX 108 = 572.4A the average flow. Power 3 = 3 = 572.4 190.8 a / Phase
- from the Main Breaker Feeder 1, MCCB 225 aT can also load and power lines buried in size 120 Sq.mm. a metal pipe (228A) can be loaded on. to install the air conditioner 1, 220V., 12,000 BTU, after all.