If opening of an expansion valve is decreased without any other changes, the refrigerant mass flow rate is reduced and evaporator pressure becomes lowered. The lowered evaporator pressure enhances heat transfer in evaporator while the reduced mass flow rate suppresses heat transfer. However, the impact of the decreased mass flow rate on the overall heat transfer coefficient becomes relatively small when refrigerant state in evaporator is two-phase state (Heo et al. 2013). This means the temperature difference term in Eq. (9) becomes larger while the overall heat transfer coefficient U does not decrease significantly. As a result, constant cooling capacity controller raises the evaporating pressure by decreasing compressor frequency to maintain the cooling capacity constant and the evaporating temperature does not decrease much.If you open the expansion valve is reduced without changing the. Namyakrop mass flow rate is reduced and pressure evaporator evaporator pressure drops will help lower heat transfer in the evaporator, while mass flow rate reduced heat transfer omit. However, the effect of the mass flow rate decreases in heat transfer coefficients by a relatively small total when the State namyakrop State in two-phase evaporator (Hao et al. 2013), which means that the phase difference of temperature in Eq. (9) will be bigger, while the heat transfer coefficients Overview U decrease significantly, so. Constant control of the cooling capacity increases by evaporating pressure compressor frequency reduction to maintain constant cooling capacity evaporating temperature and decreases.