Here is the link from internet for you and your team to understand the different benefit of the “Solidity Neutral Earthed” VS “Resistance Earthed” for the distribution transformer.

Both PPTC and SSUT, using the Solidity Neutral Earthed of the 11kV/115 kV transformer the would very sensitive to the any fault outside boundary. Such as the case on Thursday night. That the single phase to ground fault at LKB would trig the instantaneous ground over current or 50 G.

The simple solution must be set up since design, to install the Resistance earthed at the STAR point of the step up transformer. But we do not have that resistance install. We have to fight for that installation.
You may see the link in the internet for your understand of the different type of neutral earthed.
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (อังกฤษ) 1: [สำเนา]
คัดลอก!
To Manop and AllHere is the link from internet for you and your team to understand the different benefit of the "Solidity Neutral Earthed" VS "Resistance Earthed" for the distribution transformer. Both PPTC and SSUT, using the Solidity Neutral Earthed of the 11kV/115 kV transformer the would very sensitive to the any fault outside boundary. Such as the case on Thursday night. That the single phase to ground fault at LKB would trig the instantaneous ground over current or 50 G.The simple solution must be set up since design, to install the Resistance earthed at the STAR point of the step up transformer. But we do not have that resistance install. We have to fight for that installation.You may see the link in the internet for your understand of the different type of neutral earthed.
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 2:[สำเนา]
คัดลอก!
To Manop and All
Here is the link from internet for You and your Team to Understand the different Benefit of the "solidity Neutral earthed" VS "Resistance earthed" for the Distribution Transformer. Both PPTC and SSUT, using the solidity Neutral earthed of the 11KV. / 115 kV transformer the would very sensitive to the any fault outside boundary. Such as the case on Thursday night. That the single phase to Ground Fault at the LKB would trig Ground instantaneous current or over 50 G. The Simple Solution must be SET up since Design, Install to the Resistance earthed at the STAR Point of the Step up Transformer. But we do not have that resistance install. Fight for that we have to Installation. You May See the link in the internet for your Understand of the different Type of Neutral earthed.





การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: