GROUNDING AND LIGHTNING PROTECTION

GROUNDING AND LIGHTNING PROTECTION SYSTEM
General requirement
The Contractor shall supply, install, connect, test and commission a complete
system of safety grounding and lightning protection in accordance with the Drawings
and specified herein.
All metal conduits, trunking and tray systems, supports, cabinets, metal parts of
switchgear, equipment cases, motor frames electrical fittings and fixed appliances
liable to become live in the event of insulation failure, shall be effectively earthed by
means of earth continuity conductors of adequate size.
Standards and References
The grounding and lightning protection system shall comply with the following codes
and standards:
IEC 62305-1 : Protection against lightning - General principle
IEC 62305-2 : Protection against lightning - Risk management.
IEC 62305-3 : Protection against lightning - Physical damage to structures and life hazard
EIT 2003-43 : Lightning protection system against for buildings
TIS : Thai Industrial Standards
Submittals
The Contractor shall submit material lists or catalogue
for approval before purchasing
The Contractor shall submit the installation method and details
for approval before installation
Warranty
All materials and installation shall be guaranteed by the contractor at least two (2) years
years after handover.
Materials
Description
Grounding System
The material for grounding and lightning protection system shall consist of ground
rods, ground conductors, ground test boxes, lightning down conductors, lightning
roof conductors, air terminals and accessories interconnected for the complete system.
Component
Grounding System
All non-current carrying metallic parts of the electrical equipment shall be grounded.
The transformer star points shall terminate at a copper grounding conductor
bar located in the electrical room. The transformer grounding cables shall be
connected from this bar to the done by M&E's contractor. The grounding
cables shall also be connected from this bar to the ground bar of main
switchboard done by the Contractor.
All grounding conductors within power cables shall be terminated at the
switchboard ground bar by means of lugged cable connections.
Before passing through the Zero-phase-sequence current transformer, the
neutral wire shall be grounded only to the grounding busbar of the main
switchboard.
The grounding conductor size of electrical equipment shall be insulated
copper cable specified in table 19.11.1.
The connection of grounding conductor installed underground shall be done
by exothermic welding.
Ground rods shall be copper clad steel, 16 mm x 3 m.
Grounding clamps connector be able to use for ground connection installed
above ground.
Ground resistance of grounding system shall not be grater than 2 ohm.
Table 19.11.1 Minimum Size of Equipment Grounding Conductors for Electrical
Equipment



Lightning Protection System
Lightning protection shall be provided as indicated on the Drawings. The
lightning down conductor shall be terminated at ground grounding system.
The down conductor from the air termination on roof to the ground system is
preferred to install straight as possible.
The protection system shall consist of air terminals, roof conductor, down
conductors, grounding and all necessary accessories.
Air terminal shall be copper clad steel, 16 mm x 0.60 m or as specified on
the relevant drawings.

Down conductor and roof conductor shall be bare stranded copper condutor
or copper tape with the minimum cross sectional area not less then 70 mm²
or as specified on the Drawings.
The support saddle of conductor shall be fixed as the following table.

Table 19.11.2 Fixing support distance

Execution
Installation
All equipment shall be installed on the location as indicated on the Drawings and
conforming to the standard as specified.
Testing and Commissioning
The ground resistance, measured by the earth tester equipment, shall be not more
than 2 ohms.

0/5000
จาก: -
เป็น: -
ผลลัพธ์ (อังกฤษ) 1: [สำเนา]
คัดลอก!
GROUNDING AND LIGHTNING PROTECTION SYSTEM General requirement The Contractor shall supply, install, connect, test and commission a complete system of safety grounding and lightning protection in accordance with the Drawings and specified herein. All metal conduits, trunking and tray systems, supports, cabinets, metal parts of switchgear, equipment cases, motor frames electrical fittings and fixed appliances liable to become live in the event of insulation failure, shall be effectively earthed by means of earth continuity conductors of adequate size. Standards and References The grounding and lightning protection system shall comply with the following codes and standards: IEC 62305-1 : Protection against lightning - General principle IEC 62305-2 : Protection against lightning - Risk management. IEC 62305-3 : Protection against lightning - Physical damage to structures and life hazard EIT 2003-43 : Lightning protection system against for buildings TIS : Thai Industrial Standards Submittals The Contractor shall submit material lists or catalogue for approval before purchasing The Contractor shall submit the installation method and details for approval before installation Warranty All materials and installation shall be guaranteed by the contractor at least two (2) years years after handover. Materials Description Grounding System The material for grounding and lightning protection system shall consist of ground rods, ground conductors, ground test boxes, lightning down conductors, lightning roof conductors, air terminals and accessories interconnected for the complete system. Component Grounding System All non-current carrying metallic parts of the electrical equipment shall be grounded. The transformer star points shall terminate at a copper grounding conductor bar located in the electrical room. The transformer grounding cables shall be connected from this bar to the done by M&E's contractor. The grounding cables shall also be connected from this bar to the ground bar of main switchboard done by the Contractor. All grounding conductors within power cables shall be terminated at the switchboard ground bar by means of lugged cable connections. Before passing through the Zero-phase-sequence current transformer, the neutral wire shall be grounded only to the grounding busbar of the main switchboard. The grounding conductor size of electrical equipment shall be insulated copper cable specified in table 19.11.1. The connection of grounding conductor installed underground shall be done by exothermic welding. Ground rods shall be copper clad steel, 16 mm x 3 m. Grounding clamps connector be able to use for ground connection installed above ground. Ground resistance of grounding system shall not be grater than 2 ohm. Table 19.11.1 Minimum Size of Equipment Grounding Conductors for Electrical Equipment Lightning Protection System Lightning protection shall be provided as indicated on the Drawings. The lightning down conductor shall be terminated at ground grounding system. The down conductor from the air termination on roof to the ground system is preferred to install straight as possible. The protection system shall consist of air terminals, roof conductor, down conductors, grounding and all necessary accessories. Air terminal shall be copper clad steel, 16 mm x 0.60 m or as specified on the relevant drawings. Down conductor and roof conductor shall be bare stranded copper condutor or copper tape with the minimum cross sectional area not less then 70 mm² or as specified on the Drawings. The support saddle of conductor shall be fixed as the following table. Table 19.11.2 Fixing support distance Execution Installation All equipment shall be installed on the location as indicated on the Drawings and conforming to the standard as specified. Testing and Commissioning The ground resistance, measured by the earth tester equipment, shall be not more than 2 ohms.
การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 2:[สำเนา]
คัดลอก!
GROUNDING AND LIGHTNING PROTECTION SYSTEM
General Requirement
The Contractor Shall Supply, Install, Connect, Test and Commission a Complete
System of safety Grounding and lightning Protection in accordance with the Drawings
and Specified herein.
All Metal conduits, trunking and Tray Systems, supports, cabinets,. Metal Parts of
Switchgear, Equipment Cases, Motor Frames Electrical Fittings and fixed appliances
liable to become Live in the event of Insulation Failure, Shall be effectively earthed by
means of Earth continuity conductors of adequate Size.
Standards and References
The Grounding and lightning Protection System Shall. compiled with the following codes
and Standards:
IEC 62,305-1: Protection against lightning - General principle
IEC 62305-2: Protection against lightning - Risk Management.
IEC 62305-3: Protection against lightning - Physical damage to structures and Life Hazard
EIT 2003. 43: Lightning Protection System against for Buildings
TIS: Thai Industrial Standards
Submittals
The Contractor Shall submit Material Lists or Catalogue
for Approval before purchasing
The Contractor Shall submit the Installation method and details
for Approval before Installation
Warranty
All Materials and Installation Shall be guaranteed by the Contractor. at least Two (2) years
years after handover.
Materials
Description
Grounding System
The Material for Grounding and lightning Protection System Shall consist of Ground
rods, Ground conductors, Ground Test Boxes, lightning down conductors, lightning
Roof conductors, Air terminals and accessories interconnected for. Complete the System.
Component
System Grounding
All non-current carrying Metallic Parts of the Electrical Equipment Shall be grounded.
The Transformer star points Shall terminate at a Copper Grounding Conductor
Bar located in the Electrical Room. Transformer Grounding the cables Shall be
Connected to the Bar from this done by M & E Contractor's. The Grounding
cables Shall also be Connected from this Bar to the Ground Bar of main
Switchboard done by the Contractor.
All Grounding conductors Within Power cables Shall be terminated at the
Switchboard Ground Bar by means of lugged Cable Connections.
Before passing Through the Zero-phase. -sequence current Transformer, the
Neutral Grounding Wire Shall be grounded only to the busbar of the main
Switchboard.
The Grounding of Electrical Equipment Conductor Size Shall be insulated
Copper Cable Specified in Table 19.11.1.
The Connection of Grounding Conductor installed underground Shall be done.
by exothermic WELDING.
Ground rods Shall be Copper clad Steel, 16 mm x 3 M.
Grounding clamps Able to use for Ground Connection Connector be installed
above Ground.
Ground resistance of Grounding System Shall not be grater than 2 OHM.
Table Minimum 19.11.1. Size of Equipment Grounding Conductors for Electrical
Equipment Lightning Protection System Lightning Protection Shall be provided As Indicated on the Drawings. The lightning down Conductor Shall be terminated at Ground Grounding System. The down Conductor from the Air termination on Roof to the Ground System is Preferred to Install Straight As possible. The Protection System Shall consist of Air terminals, Roof Conductor, down conductors, Grounding and. all necessary accessories. Air terminal Shall be Copper clad Steel, 16 mm x 0.60 M or As Specified on the relevant DRAWINGS. Down Conductor and Roof Conductor Shall be Bare stranded Copper Condutor or Copper Tape with the Minimum cross sectional Area not Less then 70 mm². As Specified or on the Drawings. The Support Saddle of Conductor Shall be fixed As the following Table. Table 19.11.2 Support Fixing Distance Execution Installation Equipment All Shall be installed on the Location As Indicated on the Drawings and conforming to the standard As Specified. Testing and Commissioning The Ground resistance, measured by the Earth Tester Equipment, Shall not be More than 2 Ohms.




























การแปล กรุณารอสักครู่..
ผลลัพธ์ (อังกฤษ) 3:[สำเนา]
คัดลอก!
GROUNDING AND LIGHTNING PROTECTION SYSTEM

General requirement The Contractor shall supply install connect test and,,,, Commission a complete
system of safety grounding and lightning protection in accordance with the Drawings
and specified. Herein.
All, metal conduits trunking and tray systems supports cabinets metal parts,,,,, of
switchgear equipment casesMotor frames electrical fittings and fixed appliances
liable to become live in the event of, insulation failure shall. Be effectively earthed by
means of earth continuity conductors of adequate size.

Standards and References The grounding. And lightning protection system shall comply with the following codes

and standards IEC 62305-1: Protection against. Lightning - General principle
.IEC 62305-2: Protection against lightning - Risk management.
IEC 62305-3: Protection against lightning - Physical damage. To structures and life hazard
EIT 2003-43: Lightning protection system against for buildings
TIS: Thai Industrial. Standards

The Submittals Contractor shall submit material lists or catalogue
for approval before purchasing
.The Contractor shall submit the installation method and details
for approval before installation

All Warranty materials. And installation shall be guaranteed by the contractor at least two (2) years
years after handover.

, Materials Description

Grounding System The material for grounding and lightning protection system shall consist of ground
rods ground conductors,,, Ground, test boxesLightning, down conductors lightning
roof conductors air terminals, and accessories interconnected for the complete, system.


Component Grounding System All non-current carrying metallic parts of the electrical equipment shall be grounded.
. The transformer star points shall terminate at a copper grounding conductor
bar located in the electrical room.The transformer grounding cables shall be
connected from this bar to the done by M & E 's contractor. The grounding
cables. Shall also be connected from this bar to the ground bar of main
switchboard done by the Contractor.
All grounding conductors. Within power cables shall be terminated at the
switchboard ground bar by means of lugged cable connections.
.Before passing through the Zero-phase-sequence, current transformer the
neutral wire shall be grounded only to the grounding. Busbar of the main
.
switchboard The grounding conductor size of electrical equipment shall be insulated
copper cable. Specified in table 19.11.1.
The connection of grounding conductor installed underground shall be done
by exothermic welding.
.Ground rods shall be copper, clad steel 16 mm x 3 m.
Grounding clamps connector be able to use for ground connection installed.
.
above ground Ground resistance of grounding system shall not be grater than 2 ohm.
Table 19.11.1 Minimum Size of Equipment. Grounding Conductors for Equipment Electrical




Lightning Protection System
.Lightning protection shall be provided as indicated on the Drawings. The
lightning down conductor shall be terminated. At ground grounding system.
The down conductor from the air termination on roof to the ground system is
preferred to. Install straight as possible.
The protection system shall consist of air terminals roof conductor down
conductors,,,Grounding and all necessary accessories.
Air terminal shall be copper clad steel 16 mm, X 0.60 m or as specified on
the. Relevant drawings.

Down conductor and roof conductor shall be bare stranded copper condutor
or copper tape with the. Minimum cross sectional area not less then 70 mm /
or as specified on the Drawings.
The support saddle of conductor shall. Be fixed as the following table.

Table 19.11.2 Fixing support distance



Execution Installation All equipment shall be installed on the location as. Indicated on the Drawings and
conforming to the standard as specified.

Testing and Commissioning The, ground resistance. Measured by the earth, tester equipment shall be not more
than 2 ohms.

.
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.